Litcius/Paper detail

Predictive model of cooling load for ice storage air-conditioning system by using GBDT

Wanhu Zhang, Junqi Yu, Anjun Zhao, Xin-Wei Zhou

2021Energy Reports110 citationsDOIOpen Access PDF

Abstract

Cooling load prediction can provide reliable data support for the development of low energy consumption building. It is difficult for traditional models to achieve stable prediction accuracy under different load mode when the amount of data is limited. To resolve this problem, gradient boosting decision tree (GBDT) model based on selection of input variables was proposed to predict the cooling load of commercial buildings. First, the input variables that affect prediction cooling load were determined through correlation analysis on the original data set. Then, the Pearson analysis was done on the original data to get the optimal combination of input variables. Next, the ensemble learning technology was used to build GBDT model. In order to improve the prediction accuracy of the model, the grid search method was applied to determine the hyperparameter combination of GBDT. Experimental results showed that in the high-load mode, the mean absolute error (MAE) of the GBDT model was reduced by about 24% compared with the SVM, and was reduced by about 37% compared with the DNN model. Under the general load mode, MAE was reduced by about 30% and 53% respectively. Compared with the other models, the prediction accuracy of GBDT model has been significantly improved under different load mode. The proposed cooling load prediction model can provide reliable data support for the predictive control of buildings.

Topics & Concepts

Cooling loadComputer scienceHyperparameterHyperparameter optimizationMode (computer interface)Data miningSupport vector machineMachine learningAir conditioningOperating systemThermodynamicsPhysicsBuilding Energy and Comfort OptimizationUrban Heat Island MitigationWind and Air Flow Studies
Predictive model of cooling load for ice storage air-conditioning system by using GBDT | Litcius