Abstract

Abstract Under-voltage ride through (UVRT) tests can be carried out on system test benches, most of them are equipped with a converter based grid simulator. This paper describes the control of the artificial grid impedance at the 4 MW test bench at CWD. Validation measurements with the commercial wind turbine E‑115 E2 show that the virtual impedance specification is sufficient to perform UVRT tests with different grid parameters. Comparative measurements between the voltage divider based FRT Container and the grid simulator with deliberately different grid parameters show a different behavior of the research wind turbine FVA nacelle. Therefore, it is recommended to perform UVRT tests on the test bench with predefined grid parameters.