A Flexible Saturation Limiter for DC-Link Voltage Control of Grid-Forming Inverters With Enhanced Transient Stability

Cheng Luo, Xikui Ma, Teng Liu, Xiongfei Wang

2023IEEE Transactions on Energy Conversion12 citationsDOIOpen Access PDF

Abstract

This article analyzes the influence of the saturation limiter used with dc-link voltage control (DVC) on the transient stability of grid-forming (GFM) inverters and proposes a flexible saturation limiter to alleviate its adverse impact. First, it is found that the conventional saturation limiter (CSL) can enhance transient stability. Yet, it would boost the dc-link voltage or even trigger overvoltage protection, especially when the threshold value of CSL is small. To tackle the adverse impact of CSL on dc-link voltage, a flexible saturation limiter is proposed, which only begins to limit the active power reference when the derivative of dc-link voltage turns from positive to negative (the dc-link voltage reaches its peak value at this instant). Finally, experimental tests confirm the effectiveness of the scheme.

Topics & Concepts

LimiterControl theory (sociology)OvervoltageVoltageTransient (computer programming)Saturation (graph theory)GridElectric power systemConvertersMaterials scienceComputer sciencePower (physics)EngineeringElectrical engineeringPhysicsMathematicsControl (management)Artificial intelligenceCombinatoricsGeometryOperating systemQuantum mechanicsMicrogrid Control and OptimizationHVDC Systems and Fault ProtectionPower System Optimization and Stability