Microgrid Differential Protection Based on Superimposed Current Angle Employing Synchrophasors

Gagandeep Singh Dua, Barjeev Tyagi, Vishal Kumar

2022IEEE Transactions on Industrial Informatics45 citationsDOI

Abstract

The inclusion of multi-energy distributed generators (DGs), especially inverter-interfaced generators, presents challenges in the microgrid's protection strategy and operational constraints. The work for designing primary protection mechanism for microgrid is continuously progressing. In this regard, this article presents a positive sequence superimposed current differential angle based protection scheme employing only positive sequence current phasor from both ends of the line. The proposed scheme collects current phasor measurements from the low-cost microphasor measurement units ( <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex-math notation="LaTeX">$\mu$</tex-math></inline-formula> PMUs). The performance of the proposed scheme is analyzed through simulations on a seven-node microgrid in grid-connected and isolated mode operation under various fault and no-fault situations, and also considering the effect of DG penetration level and DGs types. The simulations are also carried out in the IEEE-33 node network considering C37.118.1 standards-compliant PMUs. Furthermore, a real-time control hardware-in-loop testing is performed to further validate the scheme for practical implementation.

Topics & Concepts

PhasorMicrogridFault (geology)GridReal Time Digital SimulatorComputer scienceDistributed generationPhasor measurement unitNode (physics)Units of measurementScheme (mathematics)EngineeringElectronic engineeringReliability engineeringControl theory (sociology)Electric power systemVoltageElectrical engineeringPower (physics)Control (management)MathematicsRenewable energyPhysicsGeologyGeometrySeismologyArtificial intelligenceStructural engineeringMathematical analysisQuantum mechanicsIslanding Detection in Power SystemsPower Systems Fault DetectionMicrogrid Control and Optimization
Microgrid Differential Protection Based on Superimposed Current Angle Employing Synchrophasors | Litcius