Litcius/Paper detail

A Numerical Analysis of the Fire Characteristics after Sprinkler Activation in the Compartment Fire

Ho Trong Khoat, Ji Tea Kim, Tran Dang Quoc, Ji Hyun Kwark, Hong Sun Ryou

2020Energies15 citationsDOIOpen Access PDF

Abstract

Understanding fire characteristics under sprinkler spray is valuable for performance-based safety design. However, fire characteristics during fire suppression by sprinkler spray has seldom been studied in detail. In order to present a fire suppression model by sprinkler spray and determine the fire characteristics after sprinkler activation in a compartment, a numerical analysis was conducted using a fire dynamics simulator (FDS). A simple fire suppression model by sprinkler spray was calibrated by comparing ceiling temperatures from experimental data. An extinguishing coefficient of 3.0 was shown to be suitable for the fire suppression model. The effect of sprinkler spray on the smoke layer during fire suppression was explained, revealing a smoke logging phenomenon. In addition, the smoke, which spread under the influence of the sprinkler spray, was also investigated. The temperature, velocity, and mass flow rate of the smoke layer through the doorway was significantly reduced during fire suppression compared to a free burn case.

Topics & Concepts

Fire Dynamics SimulatorSmokeEnvironmental scienceCeiling (cloud)Fire protectionFirefightingMeteorologyEngineeringWaste managementStructural engineeringChemistryCivil engineeringOrganic chemistryPhysicsFire dynamics and safety researchEvacuation and Crowd DynamicsEducation, Safety, and Science Studies