Litcius/Paper detail

Single-Phase Fault Line Selection in Distribution Network Based on Signal Injection Method

Lin Niu, Guiqing Wu, Zhangsheng Xu

2021IEEE Access65 citationsDOIOpen Access PDF

Abstract

The distribution network with small current grounding mode can ensure high power supply reliability, but it is difficult to locate single-phase grounding fault line. Most of the faults in distribution network are single-phase to ground fault. It is important to locate the fault line timely and accurately for the normal operation of the power grid. In this article, a fault line selection method based on signal injection is proposed. The dynamic selection of parameters and injection frequency in real-time monitoring distribution network by injection method is analyzed. The accuracy of signal frequency domain conversion is improved by using all phase Fourier transform. Taking the active power consumption of injected signal after fault as the criterion, the accuracy of line selection is improved. Through theoretical analysis and simulation, as well as experiments in a 600V distribution system, the fault line can be accurately selected.

Topics & Concepts

Fault (geology)SIGNAL (programming language)GroundComputer scienceFault indicatorLine (geometry)Power (physics)Frequency domainElectronic engineeringTime domainFast Fourier transformFault detection and isolationEngineeringAlgorithmElectrical engineeringMathematicsArtificial intelligencePhysicsActuatorQuantum mechanicsSeismologyProgramming languageGeologyComputer visionGeometryPower Systems Fault DetectionIslanding Detection in Power SystemsPower System Reliability and Maintenance
Single-Phase Fault Line Selection in Distribution Network Based on Signal Injection Method | Litcius