Litcius/Paper detail

Development of an experimental facility for cooling circulated water of industrial plants

Nzomjon Usmonov, Yusufbek Abdullabekov, Saodat Axmatova

2021E3S Web of Conferences11 citationsDOIOpen Access PDF

Abstract

The article discusses the installation and the hydrodynamic results analysis of three-phase fluidized bed experimental studies. An energy coefficient linear dependence of the circulating water evaporative cooler of the considered type on the irrigation coefficient has been experimentally established. The dependence of the fraction of circulating water evaporated moisture in an evaporative cooler of the type under consideration on the cooled water temperature at the inlet to the cooler and the irrigation coefficient has been established. The analysis of hydrodynamic and thermal processes occurring in a three-phase fluidized bed is carried out, and the main technological parameters for the optimal operation of installations with the specified bed are obtained in relation to solving the problem of cooling the circulating water. The dependence of the expansion of a three-phase fluidized bed on air velocity and irrigation density has been investigated. On the basis of the performed experimental studies, empirical formulas for calculations are derived.

Topics & Concepts

Evaporative coolerFluidized bedInletEnvironmental scienceWater coolingFluidized bed combustionMoistureMechanicsMaterials scienceThermodynamicsEngineeringMechanical engineeringPhysicsComposite materialRanque-Hilsch vortex tubeCyclone Separators and Fluid DynamicsProcess Optimization and Integration
Development of an experimental facility for cooling circulated water of industrial plants | Litcius