Combustion operating conditions for municipal Waste-to-Energy facilities in the U.S.
Robert Giraud, Philip H. Taylor, Chin‐Pao Huang
Abstract
This paper reports the first known comprehensive survey of combustion operating conditions across the wide range of municipal waste-to-energy facilities in the U.S. The survey was conducted in a step-wise fashion. Once the population of 188 units operating at over 70 facilities was defined, this population was stratified by distinguishing characteristics of combustion technology. Stratum-level estimates for operating conditions were determined from data collected in the survey. These stratum-level values were weighted by corresponding design capacity share and combined to infer national-level operating parameter estimates representative of the overall population. Survey results show that typical municipal waste-to-energy combustion operating conditions in the U.S. are (1) furnace temperature above 1160 °C, (2) gas residence time above 2.4 s, (3) exit gas concentrations of nearly 10% for oxygen (dry basis), and (4) over 16% for moisture. These operating parameter values can serve as benchmarks for laboratory-scale studies representative of municipal waste-to-energy combustion as typically practiced in the U.S.