Abstract

Geomagnetically induced currents (GICs) flow through grounding circuits into power systems, when triggered by geomagnetic disturbances. Power transformers (with grounding connections) are the primary path for GIC flows into power systems. The flow of GICs through a power transformer can create adverse impacts on its operation, including large increases in its reactive power demands and significant harmonic distortions in the primary side currents. This article presents case studies and analyses of the adverse impacts of GIC flows on power transformers. Presented case studies are conducted on two power transformers with different core types, power ratings, and voltage ratings. Each of these power transformers is tested for various levels of GIC flows with its loading being kept unchanged. Results of conducted case studies conclude that the <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex-math notation="LaTeX">$\text{2}$</tex-math></inline-formula> nd harmonic is the dominant in primary and side currents at all levels of GIC flows. Other harmonic components such as the <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex-math notation="LaTeX">$\text{3}$</tex-math></inline-formula> rd, <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex-math notation="LaTeX">$\text{4}$</tex-math></inline-formula> th, <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex-math notation="LaTeX">$ \text{5th},\ \text{6th},\ \text{7th}\ \text{and}\ \text{8}$</tex-math></inline-formula> th harmonic components, can be observed with lower magnitudes than the <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex-math notation="LaTeX">$\text{2}$</tex-math></inline-formula> nd harmonic component.

Topics & Concepts

Geomagnetically induced currentTransformerNotationElectrical engineeringTotal harmonic distortionTopology (electrical circuits)Computer scienceMathematicsVoltagePhysicsEngineeringEarth's magnetic fieldGeomagnetic stormQuantum mechanicsArithmeticMagnetic fieldLightning and Electromagnetic PhenomenaThermal Analysis in Power TransmissionHigh-Voltage Power Transmission Systems