Litcius/Paper detail

Analytical Calculation of Transient Short-Circuit Currents for MMC-Based MTDC Grids

Yiping Luo, Jinghan He, Meng Li, Dahai Zhang, Yongjie Zhang, Yuanwei Song, Ming Nie

2021IEEE Transactions on Industrial Electronics38 citationsDOI

Abstract

DC short-circuit current calculation is necessary to design and protect modular multilevel converter-based (MMC-based) multiterminal dc (MTDC) grids. In this article, a general and analytical short-circuit current calculation method is proposed for bipolar MTDC grids. For pole-to-pole (P2P) faults, the superposed fault equivalent network of the MTDC grid is first developed in the frequency-domain. Then, a decoupling method based on the network inductance ratio is proposed, which simplifies the high-order network into the superposition of several independent two-order <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">RLC</i> circuits. As a result, the short-circuit current can be expressed as the sum of the currents of these <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">RLC</i> circuits. For pole-to-ground (P2G) faults, the phase-domain dc line impedance considering the coupling effects is determined based on its modal-domain parameters, so that the P2G fault current can be calculated using the method of the P2P fault. The proposed method’s effectiveness is verified through simulations and experiments, and the calculation error is classified and analyzed. Compared with the existing methods, the proposed method is more accessible, more accurate, and available for hand-solution.

Topics & Concepts

Transient (computer programming)Transient analysisElectronic engineeringControl theory (sociology)Transient responseComputer sciencePhysicsMechanicsElectrical engineeringEngineeringControl (management)Operating systemArtificial intelligenceHVDC Systems and Fault ProtectionHigh-Voltage Power Transmission Systems
Analytical Calculation of Transient Short-Circuit Currents for MMC-Based MTDC Grids | Litcius