Litcius/Paper detail

A Coordinated Multi-Element Current Differential Protection Scheme for Active Distribution Systems

Vassilis C. Nikolaidis, George Michaloudis, Aristotelis M. Tsimtsios, Dimitrios Tzelepis, Campbell Booth

2022IEEE Transactions on Power Delivery29 citationsDOI

Abstract

This paper introduces a current differential protection scheme, appropriate for application in medium voltage active distribution systems, where it is desired to keep the greatest possible number of loads and DG units energized during a fault. Conventional two-terminal percentage current differential relays are used to form successive, time-current-coordinated, differential protection zones. Multiple time-delayed differential elements in each protection zone guarantee coordination with the zone's lateral protection devices, as well as between successive differential protection zones. Sensitive time-delayed differential elements protect against relatively high-resistance faults, while instantaneous differential elements minimize protection speed whenever possible. Additional emergency differential elements deal with post-fault topology changes and breaker failure conditions enhancing the overall scheme's performance. The proposed scheme is applied to a model of real medium voltage distribution system with distributed generation, considering a ring topology operation. A detailed simulation-based study proves the applicability and enhanced performance of the proposed scheme.

Topics & Concepts

Circuit breakerTopology (electrical circuits)Differential (mechanical device)Differential protectionFault (geology)Power-system protectionVoltageCurrent (fluid)Control theory (sociology)Protective relayNetwork topologyScheme (mathematics)EngineeringComputer scienceElectrical engineeringElectric power systemMathematicsPhysicsPower (physics)Computer networkSeismologyQuantum mechanicsGeologyControl (management)Artificial intelligenceTransformerAerospace engineeringMathematical analysisPower Systems Fault DetectionIslanding Detection in Power SystemsHVDC Systems and Fault Protection
A Coordinated Multi-Element Current Differential Protection Scheme for Active Distribution Systems | Litcius