Litcius/Paper detail

Detection of Failures in Metal Oxide Surge Arresters Using Frequency Response Analysis

Tiago Gonçalves Zacarias, Rafael Martins, Carlos Xavier, Júlio Cezar Oliveira Castioni, Wilson Cesar Sant’Ana, Germano Lambert‐Torres, Bruno Renó Gama, Isac Antônio dos Santos Areias, Erik Leandro Bonaldi, Frederico de Oliveira Assunção

2023Sensors12 citationsDOIOpen Access PDF

Abstract

This work presents an innovative application of Frequency Response Analysis (FRA) in order to detect early degradation of Metal Oxide Surge Arresters (MOSAs). This technique has been widely used in power transformers, but has never been applied to MOSAs. It consists in comparisons of spectra, measured at different instants of the lifetime of the arrester. Differences between these spectra are an indicator that some electrical properties of the arrester have changed. An incremental deterioration test has been performed on arrester samples (with controlled circulation of leakage current, which increases the energy dissipation over the device), and the FRA spectra correctly identified the progression of damage. Although preliminary, the FRA results seemed promising, and it is expected that this technology could be used as another diagnostic tool for arresters.

Topics & Concepts

Surge arresterLightning arresterDissipationTransformerElectrical engineeringEngineeringElectronic engineeringVoltagePhysicsThermodynamicsPower Transformer Diagnostics and InsulationHigh voltage insulation and dielectric phenomenaNon-Destructive Testing Techniques
Detection of Failures in Metal Oxide Surge Arresters Using Frequency Response Analysis | Litcius